Ventilation Rate Calculator

Calculate required ventilation airflow for indoor spaces. Determines required air changes per hour (ACH) and airflow rates based on room dimensions, occupancy…

Determines required air changes per hour (ACH) and airflow rates based on room dimensions, occupancy, activity level, and space type per ASHRAE 62.1 ventilation standards.

How are Ventilation Rates Determined?

Ventilation rate design follows ASHRAE Standard 62.1 (Ventilation for Acceptable Indoor Air Quality), which prescribes minimum outdoor air rates based on occupancy density and floor area. The goal is to dilute indoor contaminants — CO₂, VOCs, particulates, and bioaerosols — to levels that maintain occupant health and comfort.

Air Changes per Hour (ACH) indicates how many times the entire room volume is replaced with fresh air each hour. Required ACH varies by space type: offices need 4-6 ACH, classrooms 6-8 ACH, hospitals 6-12 ACH, and industrial spaces 10-30+ ACH depending on contaminant generation rates.

The ventilation rate procedure combines a per-person outdoor air rate (Rp, typically 2.5-10 L/s per person) with a per-area rate (Ra, typically 0.3-1.2 L/s per m²). Total required airflow = Rp × occupants + Ra × floor area. This dual approach accounts for both human bioeffluents and building-related contaminants.

Formula: ACH = Airflow (m³/h) / Room Volume (m³) Airflow (CFM) = ACH × Volume (ft³) / 60 ASHRAE: Vot = Rp × Pz + Ra × Az

Example Calculation

An office (10 m × 8 m × 3 m) with 20 occupants. Room volume = 240 m³. For offices, required ACH ≈ 6. Required airflow = 6 × 240 = 1440 m³/h = 400 L/s = 848 CFM. Per person: 848/20 = 42.4 CFM/person, which exceeds the ASHRAE minimum of ~20 CFM/person for offices.

When to Use This Calculator

Common Mistakes to Avoid

How to Interpret Results

Related Standards & References

Frequently Asked Questions

What is the difference between ACH and CFM?

ACH (Air Changes per Hour) is a dimensionless rate indicating how many times the room's air volume is replaced per hour — it depends on room size. CFM (Cubic Feet per Minute) is an absolute airflow measurement. A 1000 ft³ room at 6 ACH requires 100 CFM (1000×6/60), while a 5000 ft³ room at the same ACH needs 500 CFM. HVAC equipment is sized in CFM; ACH is used for design criteria.

Does higher ACH always mean better air quality?

Not necessarily. Excessive ventilation increases energy costs and can cause drafts, noise, and humidity control problems. ASHRAE 62.1 targets the minimum ACH to maintain acceptable air quality. Beyond a certain point, air filtration (HEPA, activated carbon) and source control are more effective than simply increasing air changes.