Heat Pump COP Calculator

Calculate heat pump coefficient of performance and savings. Calculates actual COP, Carnot COP, and system efficiency. When operating hours and costs are…

Calculates actual COP, Carnot COP, and system efficiency. When operating hours and costs are provided, compares heat pump vs boiler operating costs to estimate annual savings.

What is Heat Pump COP?

The Coefficient of Performance (COP) measures heat pump efficiency — the ratio of heating output to electrical input. A COP of 4.0 means the system delivers 4 kW of heating for every 1 kW of electricity consumed, effectively providing 300% 'free' energy from the environment.

COP depends primarily on the temperature difference between heat source and sink. The theoretical maximum (Carnot COP) = T_sink / (T_sink - T_source) in Kelvin. Real heat pumps achieve 40-60% of Carnot COP. Air-source heat pumps typically have COP 2.5-4.5, ground-source 3.5-5.5.

Seasonal COP (SCOP) averages performance across the entire heating season, accounting for varying outdoor temperatures. SCOP is a better indicator of real-world performance than peak COP, as COP drops significantly in very cold weather when the temperature lift is largest.

Formula: COP = Heating Output (kW) / Electrical Input (kW) Carnot COP = T_sink(K) / (T_sink(K) - T_source(K)) Carnot Efficiency = Actual COP / Carnot COP

Example Calculation

Air-source heat pump: outdoor 5°C (278K), indoor 35°C (308K). Carnot COP = 308/(308-278) = 10.27. Real COP at 45% Carnot efficiency = 4.62. Heating 10 kW output → 2.16 kW electrical input. vs Gas boiler (90% eff): 10/0.9 × gas cost. If electricity $0.15/kWh vs gas $0.06/kWh: HP cost $0.324/hr vs boiler $0.667/hr — 51% savings.

When to Use This Calculator

Common Mistakes to Avoid

How to Interpret Results

Related Standards & References

Frequently Asked Questions

At what temperature does a heat pump stop being efficient?

Most air-source heat pumps maintain COP > 2.0 down to -15°C and can operate to -25°C with newer inverter-driven compressors. Below COP 2.5-3.0, a heat pump may cost more to run than a gas boiler depending on electricity/gas price ratio. Ground-source heat pumps maintain higher COP year-round.

What is the difference between COP and EER?

COP measures heating efficiency, EER (Energy Efficiency Ratio) measures cooling efficiency. Both are output/input ratios, but EER is traditionally expressed in BTU/Wh while COP is dimensionless (kW/kW). SEER is the seasonal cooling equivalent of SCOP.